Define the BESS operating outcome
Connect the battery, BMS, PCS, EMS, protection and dispatch strategy to a clearly defined operating job.

BESS & Microgrids
Storage and microgrid solutions structured around load data, tariff, outages, renewables, site and interconnection.

Understand the system
A battery energy storage system (BESS) stores electrical energy and releases it under control when the site needs it. The deployable system combines the battery and its battery management system (BMS) with a power conversion system (PCS) that moves power between the battery's DC side and the site's AC side, a controller or energy management system (EMS) where the design needs one, and the protection, cooling, fire measures, transformer, switchgear and transfer device that let the same battery operate grid-tied, islanded during an outage, or permanently off grid.
Storage day cycle · One illustrative commercial day
Charged and readyStoring surplusCovering the peakSupporting critical load

Bescore product image · Not an installation
06:00 Dawn
Load rises before the sun. The battery waits, charged, and grid import stays well under the site limit.
12:00 Noon
Midday solar covers the load, and the energy the site cannot use goes into the battery instead of being limited.
Weak or constrained supply · Coordinate storage, renewables and generation around the site’s real limits.
18:00 Evening peak
The energy management system (EMS) discharges the battery so grid import holds at the site limit through the evening peak.
Peak demand control · Use stored energy against a measured demand profile and tariff.
22:00 Night
The transfer switch separates the site, general loads are shed, and the battery supplies the critical load until the grid returns.
Outage resilience · Keep selected critical loads available through a defined interruption.
Illustrative day, not measured data and not a record of a Metro Power installation. A real profile comes from the site’s interval data; only the loads in the approved backup design stay on during an outage.
From the example to your site
Interval demand, the tariff, outage history and the loads that must stay on determine which storage question to test first. This illustrated day cannot size your project.
The same battery chemistry sits in four very different electrical arrangements. Each one below is a single-line drawing: choose the arrangement, then change the operating condition to see where the power goes and which device acts.
While the grid is present the battery works behind the meter. It holds the site below its demand limit, stores midday solar for the evening and stops the chargers from pushing the supply past its rating. When the feeder fails, the transfer switch separates the site and the battery carries what must stay on.
What it needs that the others do notA transfer switch that separates the site from the utility within a stated time, with anti-islanding protection and an interconnection agreement with the distribution utility.
Grid available. The utility and the solar supply the site, the battery charges, and the EMS holds grid import below the site limit while the chargers run.
| Requirement | Grid-tied commercial | Weak grid or rural | Island or off grid | Utility scale |
|---|---|---|---|---|
| The converter must | Follow the grid; form the island only if the site rides through outages | Follow the grid or generator; form the island when both are away | Form the grid at every hour | Follow the grid; grid-forming where the system operator asks for it |
| Switching device | Anti-islanding protection, plus a static transfer switch where loads must stay on | ATS choosing grid or generator, plus the cabinet transfer switch | Generator changeover only | Ring main unit and MV switchgear at each station |
| Grounding | Existing site grounding; an island neutral if the site islands | Island neutral, usually through an isolation transformer | Its own grounding system | Plant and substation grounding grid |
| Approval | Utility interconnection agreement | Interconnection, plus an island protection and grounding study | Electrical permit; no interconnection | Grid connection study and the system operator’s requirements |
| Supervision | EMS on site with a cloud or SCADA view | EMS that starts and stops the generator | The hybrid inverter’s own logic | EMS control room reporting to the system operator |
BESS BENEFITS · TWO PERSPECTIVES
Battery storage can shift, support or back up energy according to a defined operating objective. The benefit changes with the owner, tariff, critical loads, renewable generation and control strategy.
01FOR THE UTILITY, SITE OR FACILITY OPERATOR
A controlled discharge strategy can reduce selected peaks or reshape site demand.
What makes it trueRequires interval data, tariff analysis and correct power/energy sizing.Storage can absorb selected solar production and release it when the operating plan calls for it.
What makes it trueDepends on generation profile, load, controls and interconnection rules.A properly designed system can support defined critical loads during eligible outage conditions.
What makes it trueBackup duration is limited by available energy, load and system configuration.BESS, solar, grid and generator resources can be dispatched as a coordinated system.
What makes it trueRequires engineered controls, protection, transition logic and operating ownership.02FOR OCCUPANTS, TENANTS OR SERVICE USERS
Critical lighting, communications, refrigeration or other designated loads may remain available during supported events.
What makes it trueOnly loads included in the approved backup design are supported.Stored solar energy can be used later instead of being limited to the moment it is generated.
What makes it trueActual benefit depends on load timing, storage capacity and dispatch.Fast controls may help the facility manage selected power transitions and operating disturbances.
What makes it truePerformance depends on the engineered system and protection scheme.Storage can enable greater renewable participation and reduced generator runtime in suitable projects.
What makes it trueEnvironmental benefit depends on the charging source and operating strategy.System architecture
Follow the journey from physical equipment to the decision a customer or operator can act on.

Lithium iron phosphate (LFP) cells, built into modules and racks, store the energy as DC. The battery management system (BMS) watches every module's voltage and temperature and sets the current the battery may safely accept or deliver.
The power conversion system (PCS) is the only link between the DC battery and the AC site. Its power rating, its overload margin and its control modes decide what the plant can do, including whether it can hold up an island when the grid is gone.
A controller decides when to charge and discharge against load, solar, generator, tariff and reserve rules. A single hybrid unit can run this logic internally; a plant with several sources or several cabinets needs a separate energy management system (EMS).

Protection, cooling, fire measures, the transfer device, the isolation transformer where one is used, and the utility interconnection make the system safe in every operating mode, not only while the grid is present.
Stored energy is coordinated by power conversion, controls, protection and the site’s real operating priorities.
02BATTERY + BMSCONTROL POINT 1Whether a grid is present, and where the solar joins the system, decides the converter's job and the site's grounding before any sizing begins.
Field realitybecomesOperational action

System to real world
Grid or renewable energy enters
Controls manage charge and state of energy
Power serves the operating priority
This visual explains system behavior. Final performance depends on approved design, field conditions, configuration and operating discipline.
Metro Power visual explainer
Use this short film as orientation, then continue into the system architecture, technical lesson or readiness action.
Connect the battery, BMS, PCS, EMS, protection and dispatch strategy to a clearly defined operating job.
The Metro Power solution
We close the gaps between the manufacturer’s product, Philippine site conditions and the people who must operate the system.

Metro Power closes the two gaps marked on the line.
Complete decision path
A solution is complete only when technical behavior, project evidence and operating ownership remain connected.
Use-case statement, load data, reserve and baseline
Interval profile, single-line diagram (SLD), studies, site and exact configuration
Hazard analysis, protection, emergency plan and authority review
Dispatch rules, acceptance tests, training and performance records
Failure modes to control
Use interval demand, critical-load and operating scenario data.
Verify supported mode, transition, protection and island tests.
Model usable energy, auxiliaries, degradation and continuing cost.
Acceptance evidence
Possible equipment paths
These are starting points for discussion, not automatic recommendations. Use the plain-language clues below to understand where each option may fit and what Metro Power still needs to confirm.

BSC-CE2-0105K0215K / BSC-CE2-0105K0200K
Evidence: Technical sheet availableManufacturer product render
Modular air-cooled cabinet for commercial, industrial and microgrid storage, published by Bescore as the CE2-105.
10 more BESS & Microgrids products

BSC-CE4-0125K0261K
Evidence: Technical sheet availableManufacturer product render
Compact liquid-cooled cabinet for commercial and industrial storage, published by Bescore as the CB4-125. Bescore now publishes this unit as BSC-CB4-0125K0261K, with the ratings below.

BSC-CD2-0050K0200K
Evidence: Availability needs checkingProduct reference image
All-in-one outdoor cabinet for solar, diesel generator and storage microgrids. Bescore's current publications do not use the CD2 code; the closest published unit is the CD-50 PV&DG, model BSC-FC2050K200K-GS, rated 50 kW and 200 kWh on the 2024 sheet, and no 100 kW / 200 kWh version is published. Metro Power confirms the current configuration with Bescore before an offer.

BSC-CB1-0500K1075K
Evidence: Availability needs checkingProduct reference image
Containerized air-cooled commercial and industrial storage, published by Bescore as the 20HC ESS, model BSC-CB10500K1075K-GS, on its 2024 sheet. It does not appear in Bescore's current product range, so Metro Power confirms availability with Bescore before an offer.

BSC-CS3-2500K5000K
Evidence: Technical sheet availableManufacturer product render
Liquid-cooled DC battery container for utility-scale storage, published by Bescore as the CS3-5000. It connects through a separate power conversion and medium-voltage station rather than at low voltage.

BSC-CE2-0105K0215K-M2B0S
Evidence: Technical sheet availableManufacturer product render
The CE2-105 platform with built-in solar charge controllers and a static transfer switch (STS), the device that moves a site between grid and island operation. Published by Bescore as the CE2-105PG.

BSC-CTC-5000K0000K
Evidence: Technical sheet availableManufacturer product render
Containerized power conversion system (PCS), the equipment that converts battery DC to grid AC, with a step-up transformer to 10, 20 or 35 kV. Published by Bescore as the CTC-5000 and paired with the CS3-5000 battery container.

BSC-CF2-0050K0100K-H
Evidence: Technical sheet availableManufacturer product render
Outdoor all-in-one cabinet combining a hybrid inverter, battery and solar input for small commercial microgrids and backup. Published by Bescore as the CF2-50 in three sizes.

OmniStax Series
Evidence: Technical sheet availableManufacturer product render
Hybrid inverter combining solar input, battery charging and discharging, generator input and backup output for small commercial microgrids. Published by Bescore as the OmniStax series, ES-29.9K-TP to ES-60K-TP.

BSC-CR1-240S1P280-G0
Evidence: Technical sheet availableManufacturer product render
Indoor battery rack of the kind fitted inside Bescore cabinets and containers, for projects that specify the battery building blocks.

BSC-CP1-016S1P280-G0
Evidence: Technical sheet availableManufacturer product render
The 14 kWh module that battery racks and cabinets are built from, for projects that specify storage down to the module.
Capacity, savings and backup duration require validated interval load, site and operating data; monthly consumption alone is insufficient. Frequency, service voltage and the largest motor to be started are confirmed before any model is proposed.
Turn learning into a decision
Move from a battery-capacity guess to a defensible use case, sizing basis and project gate.
01Leadership
Savings, resilience, renewable integration or diesel reduction require different operating and commercial logic.
Choose the primary use case02Engineering
Interval load, critical loads, outage history, solar or generator data, site and interconnection are foundational.
Assemble the sizing inputs03Finance
Model tariff, demand charges, cycling, degradation, availability, financing and avoided-cost assumptions.
Test the first assumptions04Operations
Define EMS priorities, protection, fire strategy, maintenance, incident response and operating ownership.
Build the operating conceptWhere it may fit
You do not need to choose equipment yet. If one of these situations sounds familiar, Metro Power can help define the correct starting point.
Prepare without the guesswork
These inputs help us understand the project. They are not entry requirements, and you do not need every item before contacting us.
Bills show consumption, tariff and demand charges, the starting point for testing potential value.
Time-based load data shows when power is used, which is essential for responsible power and energy sizing.
The loads that must stay on and the real outage pattern define the resilience requirement.
Existing generation changes how the battery may charge, dispatch and coordinate with the site.
The electrical arrangement and transformer capacity reveal connection limits and protection interfaces.
Space, access, fire strategy and utility rules can change whether a concept is practical.
The equipment must be published or confirmed for the service voltage and for 60 Hz operation before any model is proposed.
Existing solar changes how the battery connects and whether the inverter can keep running when the site is islanded.
In an island the battery converter alone must start the largest motor, and its overload figure, not the battery energy, decides whether it can.
Salt air affects the enclosure, cooling and corrosion protection the equipment needs.
Your next decision
Peak reduction, solar use and backup each need a different operating plan. Tell us the main job and what load records you have. Missing data is a useful starting point, not a reason to guess battery size.